From e8a92a1e9bba5eed1ed2acf6d01ea0ac6e2f9e92 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:23:13 +0900 Subject: [PATCH 01/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=208=EC=9E=A5=20=EC=9E=A5=EB=A8=B8=EB=A6=AC?= =?UTF-8?q?=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../제08장_공기조화설비공사/0-00_장머리.md | 8 +++++--- 1 file changed, 5 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/0-00_장머리.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/0-00_장머리.md index 8d1709a0..50414b9d 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/0-00_장머리.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/0-00_장머리.md @@ -5,10 +5,12 @@ PDF쪽: 745 인쇄쪽: 689 시작표지: 제8장 공기조화설비공사 끝표지: 8-1 냉동기 및 냉각탑 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +# 제8장 공기조화설비공사 From 171645be1389e84fbf42822a68bf775a5ee6547c Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:23:14 +0900 Subject: [PATCH 02/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=208-1=20=EB=83=89=EB=8F=99=EA=B8=B0=20?= =?UTF-8?q?=EB=B0=8F=20=EB=83=89=EA=B0=81=ED=83=91=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../8-01_냉동기_및_냉각탑.md | 159 +++++++++++++++++- 1 file changed, 156 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-01_냉동기_및_냉각탑.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-01_냉동기_및_냉각탑.md index 52cb0d3a..ae4e6273 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-01_냉동기_및_냉각탑.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-01_냉동기_및_냉각탑.md @@ -5,10 +5,163 @@ PDF쪽: 745~748 인쇄쪽: 689~692 시작표지: 8-1 냉동기 및 냉각탑 끝표지: 8-2 공기조화기 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 8-1 냉동기 및 냉각탑 + +### 8-1-1 냉동기 반입 + +| 작업횟수 | 1회 | | | | | | 2회 | | | | 소운반 | | 가조립 | | +|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---| +| 층별 | 지하1층 | | 지하2층 | | 지하3층 | | 지하2층 | | 지하3층 | | 10m 거리내 | | 설치기초상 | | +| 냉동
U.S.
ton
공종 | 비계공 | 특별인부 | 비계공 | 특별인부 | 비계공 | 특별인부 | 비계공 | 특별인부 | 비계공 | 특별인부 | 비계공 | 특별인부 | 비계공 | 특별인부 | +| 10 | 3 | 1 | 3 | 2 | 3 | 2 | 6 | 2 | 7 | 2 | 1 | - | 2 | - | +| 20 | 4 | 2 | 4 | 3 | 5 | 3 | 7 | 4 | 10 | 4 | 2 | - | 3 | - | +| 30 | 5 | 3 | 5 | 4 | 7 | 4 | 10 | 5 | 12 | 7 | 2 | - | 4 | 1 | +| 50 | 7 | 3 | 7 | 4 | 9 | 5 | 14 | 6 | 16 | 8 | 2 | 1 | 4 | 2 | +| 80 | 10 | 5 | 12 | 7 | 15 | 7 | 23 | 8 | 28 | 10 | 4 | 1 | 7 | 3 | +| 100 | 14 | 6 | 16 | 8 | 20 | 8 | 30 | 10 | 36 | 12 | 4 | 2 | 7 | 4 | +| 150 | 20 | 11 | 24 | 14 | 31 | 14 | 46 | 18 | 57 | 20 | 6 | 3 | 13 | 6 | +| 200 | 29 | 11 | 32 | 16 | 40 | 16 | 60 | 20 | 72 | 24 | 7 | 4 | 16 | 8 | +| 300 | 40 | 20 | 44 | 28 | 56 | 28 | 80 | 40 | 90 | 54 | 12 | 6 | 24 | 12 | +| 400 | 50 | 30 | 56 | 40 | 72 | 40 | 100 | 60 | 112 | 80 | 16 | 8 | 34 | 14 | +| 500 | 60 | 40 | 70 | 50 | 90 | 50 | 120 | 80 | 140 | 100 | 20 | 10 | 40 | 20 | +| 600 | 70 | 50 | 84 | 60 | 108 | 60 | 140 | 100 | 169 | 120 | 24 | 12 | 48 | 24 | + + + + +### 8-1-2 냉동기 설치 + +(대당) + +| 규격 | | 배관공 | 보통인부 | +|---|---|---|---| +| 왕복동식냉동기5 | 냉동톤 | 2.19 | 1.09 | +| 7.5 | 〃 | 2.80 | 1.27 | +| 15 | 〃 | 3.37 | 1.70 | +| 20 | 〃 | 3.93 | 1.98 | +| 30 | 〃 | 5.04 | 2.53 | +| 50 | 〃 | 5.91 | 3.80 | +| 80 | 〃 | 12.03 | 5.91 | + + + +[주] +① 본 품은 현장 반입 후 지하 1층 설치를 기준하였다. +② 본 품에는 시운전품이 포함되어 있다. +③ 기초 및 소운반은 제외되었다. + +### 8-1-3 냉각탑 설치 + +#### 1. 2층건물 + +| 구분 | | 1회 | | | 2회 | | +|---|---|---|---|---|---|---| +| | | 옥상 | 탑옥1층 | 탑옥3층 | 탑옥1층 | 탑옥3층 | +| 5 | 비계공 | 6 | 6 | 6 | 10 | 10 | +| | 특별인부 | 2 | 2 | 3 | 4 | 5 | +| 10 | 비계공 | 7 | 7 | 8 | 13 | 14 | +| | 특별인부 | 3 | 3 | 3 | 5 | 5 | +| 20 | 비계공 | 8 | 9 | 10 | 14 | 15 | +| | 특별인부 | 3 | 3 | 4 | 6 | 6 | +| 30 | 비계공 | 11 | 12 | 13 | 19 | 20 | +| | 특별인부 | 4 | 4 | 5 | 7 | 7 | +| 50 | 비계공 | 15 | 15 | 17 | 22 | 23 | +| | 특별인부 | 5 | 5 | 5 | 8 | 8 | +| 80 | 비계공 | 23 | 24 | 26 | 37 | 38 | +| | 특별인부 | 8 | 8 | 8 | 12 | 12 | +| 100 | 비계공 | 30 | 30 | 32 | 43 | 44 | +| | 특별인부 | 10 | 10 | 10 | 18 | 18 | +| 150 | 비계공 | 41 | 41 | 44 | 61 | 61 | +| | 특별인부 | 15 | 15 | 15 | 24 | 24 | +| 200 | 비계공 | 57 | 57 | 60 | 78 | 79 | +| | 특별인부 | 19 | 19 | 19 | 32 | 32 | +| 300 | 비계공 | 82 | 82 | 86 | 119 | 120 | +| | 특별인부 | 34 | 34 | 34 | 48 | 48 | +| 400 | 비계공 | 108 | 109 | 112 | 164 | 166 | +| | 특별인부 | 48 | 48 | 48 | 60 | 60 | +| 500 | 비계공 | 131 | 131 | 146 | 192 | 192 | +| | 특별인부 | 65 | 65 | 65 | 90 | 90 | +| 600 | 비계공 | 157 | 157 | 162 | 199 | 199 | +| | 특별인부 | 80 | 80 | 80 | 140 | 140 | + + + +#### 2. 5층건물 + +| 구분 | | 1회 | | | 2회 | | +|---|---|---|---|---|---|---| +| | | 옥상 | 탑옥1층 | 탑옥3층 | 탑옥1층 | 탑옥3층 | +| 5 | 비계공 | 7 | 7 | 8 | 11 | 12 | +| | 특별인부 | 3 | 3 | 3 | 6 | 6 | +| 10 | 비계공 | 8 | 8 | 10 | 14 | 15 | +| | 특별인부 | 4 | 4 | 4 | 6 | 6 | +| 20 | 비계공 | 9 | 10 | 11 | 15 | 16 | +| | 특별인부 | 5 | 5 | 5 | 7 | 7 | +| 30 | 비계공 | 12 | 13 | 14 | 20 | 21 | +| | 특별인부 | 6 | 6 | 6 | 8 | 8 | +| 50 | 비계공 | 16 | 17 | 18 | 24 | 25 | +| | 특별인부 | 6 | 6 | 6 | 8 | 8 | +| 80 | 비계공 | 24 | 25 | 26 | 38 | 39 | +| | 특별인부 | 10 | 10 | 10 | 13 | 13 | +| 100 | 비계공 | 32 | 32 | 33 | 45 | 46 | +| | 특별인부 | 11 | 11 | 11 | 18 | 18 | +| 150 | 비계공 | 42 | 43 | 44 | 64 | 65 | +| | 특별인부 | 17 | 17 | 17 | 24 | 24 | +| 200 | 비계공 | 55 | 56 | 57 | 79 | 80 | +| | 특별인부 | 24 | 24 | 24 | 33 | 33 | +| 300 | 비계공 | 85 | 86 | 87 | 120 | 121 | +| | 특별인부 | 35 | 35 | 35 | 49 | 49 | +| 400 | 비계공 | 112 | 113 | 114 | 169 | 170 | +| | 특별인부 | 49 | 49 | 49 | 68 | 68 | +| 500 | 비계공 | 139 | 140 | 141 | 192 | 193 | +| | 특별인부 | 63 | 63 | 63 | 92 | 92 | +| 600 | 비계공 | 155 | 156 | 157 | 201 | 202 | +| | 특별인부 | 88 | 88 | 88 | 140 | 140 | + + + +#### 3. 9층건물 + +| 구분 | | 1회 | | | 2회 | | +|---|---|---|---|---|---|---| +| | | 옥상 | 탑옥1층 | 탑옥3층 | 탑옥1층 | 탑옥3층 | +| 5 | 비계공 | 8 | 8 | 10 | 12 | 13 | +| | 특별인부 | 4 | 4 | 4 | 6 | 6 | +| 10 | 비계공 | 10 | 11 | 12 | 14 | 15 | +| | 특별인부 | 4 | 4 | 4 | 8 | 8 | +| 20 | 비계공 | 11 | 12 | 13 | 15 | 16 | +| | 특별인부 | 5 | 5 | 5 | 9 | 9 | +| 30 | 비계공 | 14 | 15 | 16 | 21 | 23 | +| | 특별인부 | 6 | 6 | 6 | 9 | 9 | +| 50 | 비계공 | 17 | 18 | 19 | 23 | 24 | +| | 특별인부 | 7 | 7 | 7 | 10 | 10 | +| 80 | 비계공 | 28 | 29 | 30 | 38 | 39 | +| | 특별인부 | 8 | 8 | 8 | 15 | 15 | +| 100 | 비계공 | 35 | 35 | 36 | 47 | 48 | +| | 특별인부 | 10 | 10 | 10 | 18 | 18 | +| 150 | 비계공 | 43 | 44 | 45 | 65 | 66 | +| | 특별인부 | 18 | 18 | 18 | 25 | 25 | +| 200 | 비계공 | 57 | 58 | 59 | 81 | 81 | +| | 특별인부 | 24 | 24 | 24 | 34 | 34 | +| 300 | 비계공 | 86 | 87 | 88 | 121 | 122 | +| | 특별인부 | 36 | 36 | 36 | 50 | 50 | +| 400 | 비계공 | 113 | 114 | 115 | 161 | 162 | +| | 특별인부 | 50 | 50 | 50 | 68 | 68 | +| 500 | 비계공 | 142 | 143 | 144 | 193 | 194 | +| | 특별인부 | 62 | 62 | 62 | 93 | 93 | +| 600 | 비계공 | 163 | 163 | 164 | 201 | 202 | +| | 특별인부 | 82 | 82 | 82 | 142 | 142 | + + + +[주] +① 탑본체, 수조 등 부속기기의 반입 및 설치를 포함한 것이다. +② 반입시 사용되는 장비의 사용료를 포함한 것이다. From aaa8eb5c8c04dd0c11dc4aa3af38475011a44366 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:25:30 +0900 Subject: [PATCH 03/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=208-2=20=EA=B3=B5=EA=B8=B0=EC=A1=B0=ED=99=94?= =?UTF-8?q?=EA=B8=B0=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../8-02_공기조화기.md | 145 +++++++++++++++++- 1 file changed, 142 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-02_공기조화기.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-02_공기조화기.md index 76c42bb6..d35ed0b1 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-02_공기조화기.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-02_공기조화기.md @@ -5,10 +5,149 @@ PDF쪽: 749~752 인쇄쪽: 693~696 시작표지: 8-2 공기조화기 끝표지: 8-3 보일러 및 방열기 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 8-2 공기조화기 + +### 8-2-1 공기가열기, 공기냉각기, 공기여과기 설치 + +(대당) + +| 규격 | | 기계설비공(인) | 보통인부(인) | +|---|---|---|---| +| 유효길이 | 610㎜ | 2.0 | 0.60 | +| | 762〃 | 2.5 | 0.75 | +| | 914〃 | 3.0 | 0.90 | +| | 1,067〃 | 3.5 | 1.00 | +| | 1,219〃 | 4.0 | 1.20 | +| | 1,372〃 | 4.5 | 1.30 | +| | 1,524〃 | 5.0 | 1.50 | +| | 1,676〃 | 5.5 | 1.60 | +| | 1,829〃 | 6.0 | 1.80 | +| | 1,981〃 | 6.5 | 1.90 | +| | 2,134〃 | 7.0 | 2.10 | +| | 2,286〃 | 7.5 | 2.20 | +| | 2,438〃 | 8.0 | 2.40 | +| | 2,591〃 | 8.5 | 2.50 | +| | 2,875〃 | 10.0 | 3.00 | +| | 3,048〃 | 11.0 | 3.30 | + + + +[주] +① 직접 팽창식(디스트리뷰터 포함)은 본 품에 30%를 가산한다. +② 헤더 분리형은 본 품에 50%를 가산한다. +③ 연결 케이싱은 납땜 시공한다. +④ 풍압이 특히 높을 경우에는 별도 계상한다. +⑤ 에로핀, 플레이트핀 및 핀피치에 상관없이 핀치수 18본 1∼3열을 기준(W254㎜×H737㎜)한 것이다. +⑥ 튜브의 본 수에 의한 증감은 2본 감할 때마다 4%씩 감하고, 2본 증할 때마다 5%씩 가산한다. + +### 8-2-2 패키지형 공기조화기 설치 + +| 작업횟수 | | 1회 | | | | | | 2회 | | | | 1회 | | | | | | +|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---| +| 층별
공종 | | 지하1층 | | 지하2층 | | 지하3층 | | 지하2층 | | 지하3층 | | 2층 | | 5층 | | 9층 | | +| 출력
(㎾) | 반입
대수 | 비계
공 | 특별
인부 | 비계
공 | 특별
인부 | 비계
공 | 특별
인부 | 비계
공 | 특별
인부 | 비계
공 | 특별
인부 | 비계
공 | 특별
인부 | 비계
공 | 특별
인부 | 비계
공 | 특별
인부 | +| 0.75이하 | 15대분 | 9.7 | 4.9 | 10.3 | 5.1 | 11.5 | 5.7 | 19.5 | 9.7 | 21.2 | 10.6 | 9.7 | 4.9 | 11.5 | 5.7 | 12.9 | 6.5 | +| 1.5 | 8 | 9.7 | 4.9 | 10.3 | 5.1 | 11.5 | 5.7 | 19.5 | 9.7 | 21.2 | 10.6 | 9.7 | 4.9 | 11.5 | 5.7 | 12.9 | 6.5 | +| 2.2 | 5 | 9.7 | 4.9 | 10.3 | 5.1 | 11.5 | 5.7 | 19.5 | 9.7 | 21.2 | 10.6 | 9.7 | 4.9 | 11.5 | 5.7 | 12.9 | 6.5 | +| 3.7 | 4 | 9.7 | 4.9 | 10.3 | 5.1 | 11.5 | 5.7 | 19.5 | 9.7 | 21.2 | 10.6 | 9.7 | 4.9 | 11.5 | 5.7 | 12.9 | 6.5 | +| 5.5 | 3 | 8.2 | 4.1 | 8.8 | 4.4 | 9.7 | 4.9 | 16.2 | 8.1 | 18.0 | 9.0 | 8.2 | 4.1 | 9.7 | 4.9 | 11.5 | 5.7 | +| 7.5 | 2 | 8.2 | 4.1 | 8.8 | 4.4 | 9.7 | 4.9 | 16.2 | 8.1 | 18.0 | 9.0 | 8.2 | 4.1 | 9.7 | 4.9 | 11.5 | 5.7 | +| 9.8 | 1 | 6.5 | 3.2 | 7.1 | 3.5 | 8.8 | 4.4 | 12.9 | 6.5 | 14.7 | 7.4 | 6.5 | 3.2 | 8.8 | 4.4 | 9.7 | 4.9 | +| 15.0 | 1 | 7.9 | 4.0 | 8.8 | 4.4 | 9.7 | 4.9 | 16.2 | 8.1 | 21.2 | 10.6 | 8.2 | 4.1 | 9.7 | 4.9 | 11.5 | 5.7 | +| 17.0 | 1 | 12.9 | 6.5 | 13.5 | 6.8 | 14.7 | 7.4 | 25.9 | 13.0 | 26.5 | 13.3 | 12.9 | 6.5 | 14.7 | 7.4 | 16.2 | 8.1 | +| 20.0 | 1 | 14.7 | 7.4 | 15.3 | 7.7 | 16.2 | 8.1 | 29.2 | 14.6 | 30.9 | 15.5 | 14.7 | 7.4 | 16.2 | 8.1 | 18.0 | 9.0 | +| 37.0 | 1 | 25.9 | 13.0 | 26.5 | 13.3 | 27.7 | 13.8 | 51.9 | 25.9 | 53.7 | 26.8 | 25.9 | 13.0 | 27.7 | 13.8 | 29.2 | 14.6 | + + + + +[주] +① 반입 및 설치품을 포함한 것이다. +② 반입시 사용되는 장비사용료를 포함한 것이다. + +### 8-2-3 공기조화기(Air Handling Unit) 설치 + +(대당) + +| 규격 | | 기계설비공(인) | 보통인부(인) | +|---|---|---|---| +| 1) 수냉식 패키지형 | | | | +| 압축기전동기출력 | 0.75㎾ 이하 | 0.5 | 0.5 | +| | 1.1㎾이하 | 0.6 | 0.6 | +| | 1.5㎾이하 | 1.0 | 1.0 | +| | 2.2㎾이하 | 1.3 | 1.3 | +| | 3.7㎾이하 | 1.5 | 1.5 | +| | 10.8㎾이하 | 2.0 | 2.0 | +| | 30.0㎾이하 | 3.0 | 3.0 | +| | 37.0㎾이하 | 3.5 | 3.5 | + +| 2) 공냉식 패키지형 | | | | +| 압축기전동기출력 | 2.2㎾이하 | 1.0 | 1.0 | +| | 3.7㎾이하 | 1.3 | 1.3 | +| | 7.5㎾이하 | 1.5 | 1.5 | +| 3) 핸들링유닛전동기출력 | 7.5㎾이하 | 4.0 | 1.2 | +| 〃 | 15㎾ 이하 | 6.0 | 1.8 | +| 〃 | 15㎾ 이상 | 7.0 | 2.5 | +| 4) 팬코일유닛(床置형)풍량 | 510㎥/hr이하 | 1.0 | | +| 〃 | 680㎥/hr이상 | 1.0 | 0.2 | +| 팬코일유닛(天井형) | 510㎥/hr이하 | 1.5 | 0.5 | +| 〃 | 680㎥/hr이상 | 2.0 | 0.5 | +| 5) 윈도우타입 | 0.4㎾이하 | 1.0 | 0.5 | +| 〃 | 0.55㎾ 이하 | 1.3 | 0.5 | +| 〃 | 0.75㎾ 이하 | 1.5 | 1.0 | + + + +[주] +① 조립 및 부속품 설치품을 포함한다. +② 수배관 전기배관품은 포함하지 않았다. +③ 운반품 및 가대는 별도 계상한다. +④ 핸들링유닛설치에는 가열기 또는 냉각기 설치품이 제외되었다. + +### 8-2-4 천장형 에어컨 설치('20년 신설) + +(대당) + +| 구분 | 단위 | 수량 (냉방능력 kW) | | | +|---|---|---|---|---| +| | | 실내기 | 실외기 | | +| | | 16이하 | 6~12이하 | 16이하 | +| 기계설비공 | 인 | 0.45 | 1.00 | 1.33 | +| 보통인부 | 인 | 0.22 | 0.50 | 0.67 | +| 비고 | - 본 품의 실외기는 실내기 1대 연결기준이며, 실내기 추가로 인해 실외기에 배관접합이 추가되는 경우, 실내기 대당 실외기 품의 15%를 가산한다. | | | | + + + +[주] +① 본 품은 천장에 설치하는 에어컨 실내기와 바닥에 상치하는 에어컨 실외기 설치 기준이다. +② 실내기는 위치선정, 앵커 및 달대 설치, 실내기 및 커버 설치, 제어부 결선, 배관접합 작업을 포함한다. +③ 실외기는 위치선정, 실외기 설치, 배관접합, 냉매진공 및 충전, 작동시험을 포함한다. +④ 배관 설치 및 보온, 전기・통신배선 작업은 별도 계상한다. +⑤ 장비(크레인, 냉매가스 충전기 등)는 별도 계상한다. +⑥ 공구손료 및 경장비(전동드릴 등) 기계경비는 인력품의 2%로 계상한다. + +### 8-2-5 전열교환기 설치('20년 신설) + +(대당) + +| 구분 | 단위 | 수량 (풍량 ㎥/h) | | | +|---|---|---|---|---| +| | | 250이하 | 500이하 | 800이하 | +| 기계설비공 | 인 | 0.21 | 0.28 | 0.36 | +| 보통인부 | 인 | 0.12 | 0.16 | 0.20 | + + + +[주] +① 본 품은 천장에 설치하여 덕트와 연결하는 환기시스템(전열교환기) 기준이다. +② 본 품은 앵커 및 달대 설치, 전열교환기 설치, 덕트연결(4구), 제어부 결선, 작동시험을 포함한다. +③ 덕트공사(덕트 설치, 취출구 등) 및 전기・통신배선 작업은 별도 계상한다. +④ 공구손료 및 경장비(전동드릴 등)의 기계경비는 인력품의 2%로 계상한다. From 870646c2938c8efb130e81296c843fabffdff9d9 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:28:19 +0900 Subject: [PATCH 04/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=208-3=20=EB=B3=B4=EC=9D=BC=EB=9F=AC=20?= =?UTF-8?q?=EB=B0=8F=20=EB=B0=A9=EC=97=B4=EA=B8=B0=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../8-03_보일러_및_방열기.md | 127 +++++++++++++++++- 1 file changed, 124 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-03_보일러_및_방열기.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-03_보일러_및_방열기.md index ed62f78f..58631783 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-03_보일러_및_방열기.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-03_보일러_및_방열기.md @@ -5,10 +5,131 @@ PDF쪽: 752~754 인쇄쪽: 696~698 시작표지: 8-3 보일러 및 방열기 끝표지: 8-4 온수기 및 온수분배기 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 8-3 보일러 및 방열기 + +### 8-3-1 보일러 설치 + +| 규격 | | 단위 | 보일러공 | 특별인부 | +|---|---|---|---|---| +| 주철제
보일러 | 1호(20∼60미만) 1,000Kcal/hr | 인/절 | 0.90 | 0.30 | +| | 2호(60∼135미만) 〃 | 〃 | 1.10 | 0.30 | +| | 3호(135∼230미만)〃 | 〃 | 1.10 | 0.30 | +| | 4호(230∼330미만)〃 | 〃 | 2.10 | 0.50 | +| | 5호(330∼640미만)〃 | 〃 | 3.0 | 0.70 | +| | 6호(640∼1,180미만) 〃 | 〃 | 4.5 | 0.70 | +| 강판제보일러 | | 인/중량톤 | 1.2 | 0.8 | +| 패키지형수관식보일러 | | 인/중량톤 | 6.0 | 2.0 | + + + +[주] +① 각 보일러 품은 지면과 동일한 평면에 설치하는 경우이며 운반자동차가 설치위치까지 들어가지 못할 시는 하치장에서의 반입비는 별도 계상한다. +② 조립, 설치, 수압시험 및 시운전 등을 포함한다. +③ 강판제 및 패키지형 보일러는 내화시설품이 포함되었다. +④ 산업용 보일러 설치는 ‘[기계설비부문] 13-5-1 보일러 설치’를 따른다. + +### 8-3-2 경유보일러 설치 + +(대당) + +| 규격 | 배관공 | 보통인부 | +|---|---|---| +| 15,000 Kcal/hr | 1.00 | 0.39 | + +[주] +① 수압시험, 시운전품은 본 품에 포함되어 있다. +② 소운반은 별도 계상한다. + +### 8-3-3 가스보일러(가정용) 설치('92년 신설, '16, '20년 보완) + +(대당) + +| 구분 | 단위 | 수량 | | | | | +|---|---|---|---|---|---|---| +| | | 13,000
Kcal/hr | 16,000
Kcal/hr | 20,000
Kcal/hr | 25,000
Kcal/hr | 30,000
Kcal/hr | +| 보일러공 | 인 | 0.845 | 0.952 | 1.028 | 1.123 | 1.218 | +| 보통인부 | 인 | 0.164 | 0.184 | 0.199 | 0.217 | 0.236 | +| 비고 | - 바닥설치형은 본 품에 15%를 감한다. | | | | | | + + + +[주] +① 본 품은 세대내 벽걸이형 가스보일러 설치 기준이다. +② 본 품은 보일러 설치, 연도용 슬리브, 배기팬 설치 및 접속부의 기밀유지, 수압시험 및 시운전을 포함한다. +③ 보일러 하부 마감재(배관 커버 등)가 필요한 경우 별도 계상한다. + +### 8-3-4 온수보일러 설치('98년 신설) + +(대당) + +| 규격 | 보일러공 | 특별인부 | +|---|---|---| +| 70×1,000kcal/hr이하 | 1.46 | 0.58 | +| 120 〃 | 2.06 | 0.83 | +| 150 〃 | 2.47 | 0.99 | +| 240 〃 | 3.03 | 1.22 | +| 360 〃 | 3.85 | 1.54 | + +[주] +① 본 품은 온수보일러를 조립 및 설치하는 품으로 수압시험이 포함되어 있다. +② 기초공사, 반입 및 시운전은 현장여건에 따라 필요시 별도 계상한다. + +### 8-3-5 전기보일러 설치('03년 신설) + +(대당) + +| 규격 | 보일러공 | 비계공 | +|---|---|---| +| 135,000kcal (30㎾) | 3.8 | 2.3 | + +[주] +① 본 품은 축열식심야 전기보일러, 실내온도조절기 설치기준으로 시운전 및 소운반이 포함되어 있다. +② 본 품에는 팽창탱크, 안전핀, 순환펌프 설치가 포함되었으며, 기초공사, 전선관, 전기배선은 별도 계상한다. +③ 사용장비는 다음기준에 따라 적용한다. + +| 장비명 | 규격 | 사용기간 | +|---|---|---| +| 트럭탑재형 크레인 | 5톤 | 3hr | + +### 8-3-6 방열기('07년 보완) + +| 규격 | 단위 | 배관공 | 보통인부 | +|---|---|---|---| +| 주철재 바닥설치 20절 이하 | 인/조 | 1.10 | 0.10 | +| 21절 이상 | 인/조 | 1.50 | 0.10 | +| 벽걸이 3절 | 인/조 | 1.60 | 0.20 | +| 천장달기 3절 | 인/조 | 2.50 | 0.50 | +| 1m 길트 | 인/본 | 0.70 | 0.10 | +| 콘백터 길이 1m 미만 | 인/조 | 0.80 | 0.10 | +| 1m 이상 | 인/조 | 1.10 | 0.10 | +| 베이스보드 1단형길이 2m 미만 | 인/단 | 1.90 | 0.20 | +| 2m이상 | 인/단 | 2.40 | 0.20 | +| 강판제 및 알루미늄제 방열기 1m 미만 | 인/조 | 0.44 | 0.06 | +| 1m 이상 | 인/조 | 0.60 | 0.06 | + +[주] +① 본체, 밸브, 트랩류(강판제 및 알루미뉴제 방열기 제외) 등 지지철물 설치, 소운반, 기밀시험 및 공기빼기 품이 포함되어 있다 +② 벽걸이 3절 초과하는 경우 매 1절 증가마다 15%씩 가산한다. +③ 콘백터 및 베이스 보드는 1단 증가마다 20%씩 가산한다. +④ 패널 라디에이터(panel radiator)는 콘백터 품을 적용한다. + +### 8-3-7 전기콘벡터 설치('20년 신설) + +(대당) + +| 구분 | 단위 | 수량 | +|---|---|---| +| 기계설비공 | 인 | 0.09 | + +[주] +① 본 품은 벽걸이형 전기콘벡터(740×440×105mm) 설치 기준이다. +② 본 품에는 브라켓 설치, 콘벡터 설치 작업을 포함한다. +③ 공구손료 및 경장비(전동드릴 등)의 기계경비는 인력품의 3%로 계상한다. From 32b7c1b3e2675c2d7020bada334df68c76b5a910 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:28:20 +0900 Subject: [PATCH 05/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=208-4=20=EC=98=A8=EC=88=98=EA=B8=B0=20?= =?UTF-8?q?=EB=B0=8F=20=EC=98=A8=EC=88=98=EB=B6=84=EB=B0=B0=EA=B8=B0=20?= =?UTF-8?q?=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../8-04_온수기_및_온수분배기.md | 56 ++++++++++++++++++- 1 file changed, 53 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-04_온수기_및_온수분배기.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-04_온수기_및_온수분배기.md index 0f8c8530..ebb19ace 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-04_온수기_및_온수분배기.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-04_온수기_및_온수분배기.md @@ -5,10 +5,60 @@ PDF쪽: 754~755 인쇄쪽: 698~699 시작표지: 8-4 온수기 및 온수분배기 끝표지: 8-5 탱크 및 헤더 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 8-4 온수기 및 온수분배기 + +### 8-4-1 전기온수기 설치('03년 신설) + +(대당) + +| 규격 | 보일러공 | 비계공 | +|---|---|---| +| 350ℓ | 2.0 | 0.3 | + +[주] +① 본 품은 축열식심야 전기온수기 설치기준으로 시운전 및 소운반이 포함되어 있다. +② 본 품에는 안전핀, 감압밸브 설치가 포함되었으며 기초공사, 전선관, 전기배선은 별도 계상한다. + +### 8-4-2 전기온수기(벽걸이형) 설치('20년 신설) + +(대당) + +| 구분 | 단위 | 수량 | | | +|---|---|---|---|---| +| | | 15L | 30L | 50L | +| 보일러공 | 인 | 0.17 | 0.18 | 0.23 | +| 보통인부 | 인 | 0.07 | 0.08 | 0.09 | + + + +[주] +① 본 품은 벽걸이형 전기온수기 설치 기준이다. +② 본 품에는 브라켓 설치, 전기온수기 설치, 시운전 작업을 포함한다. +③ 배관 및 밸브 등 부속 설치, 보온, 지지대 설치는 별도 계상한다. +④ 전선관, 전기배선은 별도 계상한다. +⑤ 공구손료 및 경장비(전동드릴 등)의 기계경비는 인력품의 2%로 계상한다. + +### 8-4-3 온수분배기 설치('13년 보완) + +(개당) + +| 구분 | 단위 | 수량 (규격) | | | | | | +|---|---|---|---|---|---|---|---| +| | | 2구 | 3구 | 4구 | 5구 | 6구 | 7구 | +| 배관공 | 인 | 0.286 | 0.339 | 0.391 | 0.432 | 0.471 | 0.506 | +| 보통인부 | 인 | 0.150 | 0.173 | 0.194 | 0.211 | 0.226 | 0.239 | + + + +[주] +① 본 품의 규격은 공급 및 환수 헤더 개수 기준이며 퇴수구는 제외한다. +② 온수분배기의 조립, 설치, 배관연결, 밸브 및 커넥터 설치, 배관시험을 포함한다. +③ 공구손료 및 경장비(전동드릴 등)의 기계경비는 인력품의 2%로 계상하다. From 12aa14ab9b2e7cec72ebbac93f73415a9dd54a52 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:28:21 +0900 Subject: [PATCH 06/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=208-5=20=ED=83=B1=ED=81=AC=20=EB=B0=8F=20?= =?UTF-8?q?=ED=97=A4=EB=8D=94=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../8-05_탱크_및_헤더.md | 23 ++++++++++++++++--- 1 file changed, 20 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-05_탱크_및_헤더.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-05_탱크_및_헤더.md index edd2140b..7282ada6 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-05_탱크_및_헤더.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-05_탱크_및_헤더.md @@ -5,10 +5,27 @@ PDF쪽: 755 인쇄쪽: 699 시작표지: 8-5 탱크 및 헤더 끝표지: 8-6 부수장비 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 8-5 탱크 및 헤더 + +### 8-5-1 오일서비스탱크 설치 + +| 탱크용량 (ℓ) | 배관공 | 보통인부 | +|---|---|---| +| 100 | 0.75 | 0.90 | +| 200 | 0.98 | 1.05 | +| 300 | 1.13 | 1.28 | +| 400 | 1.50 | 1.50 | +| 500 | 1.50 | 1.50 | +| 750 | 2.10 | 2.10 | +| 1,000 | 2.63 | 2.63 | + +[주] +본 품에는 가대설치품이 포함되어 있다. From fe7088ac445a0a98d19f14b50aaf292faaba94c5 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:28:22 +0900 Subject: [PATCH 07/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=208-6=20=EB=B6=80=EC=88=98=EC=9E=A5=EB=B9=84?= =?UTF-8?q?=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../제08장_공기조화설비공사/8-06_부수장비.md | 39 +++++++++++++++++-- 1 file changed, 36 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-06_부수장비.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-06_부수장비.md index 1387c5ab..8a4fa671 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-06_부수장비.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제08장_공기조화설비공사/8-06_부수장비.md @@ -5,10 +5,43 @@ PDF쪽: 756 인쇄쪽: 700 시작표지: 8-6 부수장비 끝표지: 제9장 기타공사 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 8-6 부수장비 + +### 8-6-1 로터리 오일 버너 + +| 전동기
전력
(㎾) | 로터리오일버너
(수동식) | | 로터리오일버너
(반자동식) | | 로터리오일버너
(전자동식)(on off) | | 로터리오일버너
(전자동식)(비례) | | +|---|---|---|---|---|---|---|---|---| +| | 기계설비공
(인) | 특별인부
(인) | 기계설비공
(인) | 특별인부
(인) | 기계설비공
(인) | 특별인부
(인) | 기계설비공
(인) | 특별인부
(인) | +| 0.4이하 | 2.5∼3.0 | 1.0∼1.2 | 4.2∼5.0 | 1.4∼1.7 | 5.0∼6.0 | 1.7∼2.0 | 5.9∼7.1 | 2.0∼2.4 | +| 0.55이하 | 2.7∼3.2 | 1.2∼1.4 | 4.5∼5.0 | 2.0∼2.4 | 5.4∼6.5 | 2.4∼2.9 | 6.3∼7.6 | 2.8∼3.4 | +| 0.75이하 | 3.0∼3.6 | 1.4∼1.7 | 5.0∼6.0 | 2.3∼2.8 | 6.0∼7.2 | 2.7∼3.2 | 7.0∼8.4 | 3.2∼3.8 | +| 1.5이하 | 3.3∼4.0 | 1.5∼1.8 | 5.5∼6.6 | 2.5∼3.0 | 6.6∼7.9 | 3.0∼3.6 | 7.7∼9.2 | 3.5∼4.2 | + + + +[주] +① 수동식에는 유량조절기, 오일프리히터, 2차공기주입구, 철물 등을 포함한다. +② 반자동식에는 수동의 부속품 조작기, 압력스위치 또는 광전관저수위 스위치 등을 포함한다. +③ 전자동식 ON-OFF에는 반자동의 부속품, 착화장치, 댐퍼컨트롤러 등을 포함하고 비례제어에는 전자동 ON-OFF의 부속품의 모지트럴, 컨트롤, 오요터, 비례압력, 조절기품 등을 포함한다. + +### 8-6-2 건타입 오일버너 + +(대당) + +| 규격 | 보일러공 | 특별인부 | +|---|---|---| +| 건타입 오일버너 0.75㎾ | 4.2 | 2.0 | +| 1.5 | 4.6 | 2.2 | +| (전자동방식) 2.2 | 5.0 | 2.5 | +| 3.7 | 6.0 | 3.0 | + +[주] +조립, 설치, 수압시험 및 시운전 등을 포함한다. From 214b0a71512175742c747940e6014185160b4ef5 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:08 +0900 Subject: [PATCH 08/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B1=B4=EC=B6=95=20=EC=A0=9C10=EC=9E=A5?= =?UTF-8?q?=20=EC=9E=A5=EB=A8=B8=EB=A6=AC=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit - PDF 685쪽 · pum_md_tool check 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 Co-Authored-By: Claude Opus 5 (1M context) Claude-Session: https://claude.ai/code/session_016WRFJmmhPi4exAzHgPZHMT --- .../03_건축부문/제10장_창호_및_유리공사/0-00_장머리.md | 8 +++++--- 1 file changed, 5 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/0-00_장머리.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/0-00_장머리.md index f3bbaff4..6d61303e 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/0-00_장머리.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/0-00_장머리.md @@ -5,10 +5,12 @@ PDF쪽: 685 인쇄쪽: 629 시작표지: 제10장 창호 및 유리공사 끝표지: 10-1 창호 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_laptop_3 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +# 제10장 창호 및 유리공사 From 13d10e96cd50d2720608741b18338a8c1096acfa Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:09 +0900 Subject: [PATCH 09/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B1=B4=EC=B6=95=2010-1=20=EC=B0=BD?= =?UTF-8?q?=ED=98=B8=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit - PDF 685~687쪽(인쇄 629~631쪽) · pum_md_tool check 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 Co-Authored-By: Claude Opus 5 (1M context) Claude-Session: https://claude.ai/code/session_016WRFJmmhPi4exAzHgPZHMT --- .../제10장_창호_및_유리공사/10-01_창호.md | 154 +++++++++++++++++- 1 file changed, 151 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-01_창호.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-01_창호.md index 3d70ae41..1460d76c 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-01_창호.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-01_창호.md @@ -5,10 +5,158 @@ PDF쪽: 685~687 인쇄쪽: 629~631 시작표지: 10-1 창호 끝표지: 10-2 부속자재 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_laptop_3 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 10-1 창호 + +### 10-1-1 목재창호 설치('14, '20년 보완) + +(개소당) + +| 구분 | | 단위 | 수량 | | | | +|---|---|---|---|---|---|---| +| | | | 1.0㎡이하 | 1.0∼3.0㎡이하 | 3.0∼6.0㎡이하 | 6.0∼8.0㎡이하 | +| 여닫이 | 창호공 | 인 | 0.261 | 0.313 | 0.431 | 0.554 | +| | 보통인부 | 인 | 0.056 | 0.064 | 0.088 | 0.113 | +| 미서기
(단창) | 창호공 | 인 | 0.248 | 0.297 | 0.409 | 0.526 | +| | 보통인부 | 인 | 0.054 | 0.061 | 0.084 | 0.108 | +| 비고 | - 문선을 설치하는 경우 다음 품을 추가 계상한다. | | | | | | + + +(m당) + +| 구분 | 단위 | 수량 | +|---|---|---| +| 창호공 | 인 | 0.010 | + + +[주] +① 본 품은 목재창호의 조립 및 설치 기준이다. +② 본 품은 창호틀(내틀, 스토퍼, 레일 등) 조립 및 설치, 창호짝 설치, 부속철물(경첩, 문달기) 설치 및 마무리 작업을 포함한다. +③ 공구손료 및 경장비(전동대패, 전동드라이버 등)의 기계경비는 인력품의 3%로 계상한다. + +### 10-1-2 강재창호 설치('14, '20년 보완) + +(개소당) + +| 구분 | 단위 | 수량 | | | | +|---|---|---|---|---|---| +| | | 1.0㎡이하 | 1.0∼3.0㎡이하 | 3.0∼6.0㎡이하 | 6.0∼8.0㎡이하 | +| 창호공 | 인 | 0.393 | 0.432 | 0.560 | 0.658 | +| 보통인부 | 인 | 0.094 | 0.103 | 0.134 | 0.157 | + + +[주] +① 본 품은 여닫이 강재창호 설치 기준이다. +② 본 품은 창호틀 설치, 창호짝 설치, 부속철물(경첩) 설치 및 마무리 작업을 포함한다. +③ 공구손료 및 경장비(용접기, 전동드릴, 그라인더 등)의 기계경비는 인력품의 3%로 계상한다. + +### 10-1-3 알루미늄창호 설치('14, '20, '26년 보완) + +(개소당) + +| 구분 | 단위 | 수량 | | | | | +|---|---|---|---|---|---|---| +| | | 1.0㎡이하 | 1.0∼3.0㎡
이하 | 3.0∼6.0㎡
이하 | 6.0∼9.0㎡
이하 | 9.0∼12.0㎡
이하 | +| 창호공 | 인 | 0.208 | 0.283 | 0.403 | 0.471 | 0.512 | +| 보통인부 | 인 | 0.047 | 0.063 | 0.084 | 0.108 | 0.116 | +| 비고 | - FIX창, 루버창 등 창호짝 설치가 필요 없는 경우 본 품의 15%를 감하여 적용한다. | | | | | | + + +[주] +① 본 품은 미서기, 프로젝트창 등 알루미늄창호 설치 기준이다. +② 본 품은 앵커 및 연결철물 설치, 창호(틀, 짝) 설치, 마무리 작업을 포함한다. +③ 공구손료 및 경장비(드릴 등)의 기계경비는 인력품의 2%로 계상한다. + +### 10-1-4 조립식 알루미늄창호 설치('26년 신설) + +(㎡당) + +| 구분 | 단위 | 수량 | +|---|---|---| +| 창호공 | 인 | 0.074 | +| 보통인부 | 인 | 0.029 | + + +[주] +① 본 품은 일정 크기의 유닛으로 조립된 부재(폭 1.5m이하)를 반입하여 현장에서 연속적으로 설치하는 AL창호(연창) 기준이다. +② 본 품은 앵커 및 연결철물 설치, 창호(틀, 짝) 설치, 마무리 작업을 포함한다. +③ 알루미늄 프레임을 스틱월방식으로 조립해서 설치하는 경우 ‘[건축부문] 10-1-8 커튼월 프레임 설치’를 따른다. +④ 공구손료 및 경장비(드릴 등)의 기계경비는 인력품의 2%로 계상한다. + +### 10-1-5 합성수지창호 설치('14년 신설, '20년 보완) + +(개소당) + +| 구분 | | 단위 | 수량 | | | | | +|---|---|---|---|---|---|---|---| +| | | | 1.0㎡이하 | 1.0∼3.0㎡
이하 | 3.0∼6.0㎡
이하 | 6.0∼9.0㎡
이하 | 9.0∼12.0㎡
이하 | +| 단창 | 창호공 | 인 | 0.169 | 0.210 | 0.337 | 0.413 | 0.468 | +| | 보통인부 | 인 | 0.037 | 0.046 | 0.068 | 0.091 | 0.104 | +| 이중창 | 창호공 | 인 | 0.200 | 0.247 | 0.381 | 0.476 | 0.542 | +| | 보통인부 | 인 | 0.044 | 0.055 | 0.085 | 0.106 | 0.121 | + + +[주] +① 본 품은 미서기 합성수지창호 설치 기준이다. +② 본 품은 앵커 및 연결철물 설치, 창호(틀, 짝) 설치, 마무리 작업을 포함한다. +③ 공구손료 및 경장비(전동드릴 등)의 기계경비는 인력품의 2%로 계상한다. + +### 10-1-6 셔터설치(장치포함)('20년 보완) + +(개소당) + +| 구분 | 단위 | 수량 | | | | | +|---|---|---|---|---|---|---| +| | | 5㎡미만 | 5∼10㎡미만 | 10∼15㎡미만 | 15∼20㎡미만 | 20∼25㎡미만 | +| 창호공 | 인 | 2.35 | 2.94 | 3.53 | 4.12 | 4.71 | +| 보통인부 | 인 | 0.79 | 0.99 | 1.19 | 1.39 | 1.58 | + + +[주] +① 본 품은 전동셔터(강재, AL) 설치 기준이다. +② 본 품은 가이드레일, 샤프트, 전동개폐기, 셔터 및 셔터박스 설치 작업을 포함한다. +③ 공구손료 및 경장비(용접기, 전기그라인더 등)의 기계경비는 인력품의 2%로 계상한다. + +### 10-1-7 자동문 설치('26년 신설) + +(개소당) + +| 구분 | 단위 | 수량 | +|---|---|---| +| 창호공 | 인 | 0.85 | +| 기계설비공 | 인 | 0.75 | +| 보통인부 | 인 | 0.47 | + + +[주] +① 본 품은 보행자용 자동문(미닫이유리문)의 설치 기준이다. +② 본 품은 스테인리스 프레임 설치, 구동장치(오퍼레이터 등) 및 감지센서 설치, 작동시험 작업을 포함한다. +③ 유리공사, 전기 및 통신공사는 별도 계상한다. +④ 공구손료 및 경장비(용접기 등)의 기계경비는 인력품의 2%로 계상한다. + +### 10-1-8 커튼월 프레임 설치('14, '20, '26년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 시공량(kg) | | +|---|---|---|---|---| +| | | | 현장가공 | 공장가공 | +| 창호공 | 인 | 3 | 130 | 150 | +| 보통인부 | 인 | 1 | | | + + +[주] +① 본 품은 커튼월의 알루미늄 프레임을 스틱월방식으로 조립해서 설치하는 기준이다. +② 현장가공은 현장에서 프레임(BAR)을 제작하여 설치하는 기준이다. +③ 공장가공은 공장에서 제작된 프레임(BAR)을 반입하여 조립하는 기준이다. +④ 본 품은 먹매김, 구멍뚫기 및 앵커철물 설치, 브라켓 조립 및 프레임 설치 작업을 포함한다. +⑤ 비계매기 또는 고소작업차 비용은 필요시 별도 계상한다. +⑥ 외벽의 높이에 따른 할증은 ‘[공통부문] 1-4-5 위험’을 따른다. +⑦ 공구손료 및 경장비(절단기, 전동드릴 등)의 기계경비는 3%로 계상한다. From 8c2018a784bfb6e6595187cfab26c85ae5cbe850 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:09 +0900 Subject: [PATCH 10/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B1=B4=EC=B6=95=2010-2=20=EB=B6=80?= =?UTF-8?q?=EC=86=8D=EC=9E=90=EC=9E=AC=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit - PDF 687~688쪽(인쇄 631~632쪽) · pum_md_tool check 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 Co-Authored-By: Claude Opus 5 (1M context) Claude-Session: https://claude.ai/code/session_016WRFJmmhPi4exAzHgPZHMT --- .../제10장_창호_및_유리공사/10-02_부속자재.md | 59 ++++++++++++++++++- 1 file changed, 56 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-02_부속자재.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-02_부속자재.md index a15074a3..c7f38d6c 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-02_부속자재.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-02_부속자재.md @@ -5,10 +5,63 @@ PDF쪽: 687~688 인쇄쪽: 631~632 시작표지: 10-2 부속자재 끝표지: 10-3 유리 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_laptop_3 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 10-2 부속자재 + +### 10-2-1 도어체크 설치('20년 보완) + +(10개소당) + +| 구분 | 단위 | 수량 | +|---|---|---| +| 창호공 | 인 | 0.62 | +| 보통인부 | 인 | 0.31 | + + +[주] +① 본 품은 여닫이문의 도어체크 설치 기준이다. +② 본 품은 도어체크 조립(브라켓, 링크, 바디) 및 설치를 포함한다. +③ 공구손료 및 경장비(전동드릴 등)의 기계경비는 인력품의 2%로 계상한다. + +### 10-2-2 플로어힌지 설치('20년 보완) + +(10개소당) + +| 구분 | 단위 | 수량 | +|---|---|---| +| 창호공 | 인 | 0.96 | +| 보통인부 | 인 | 0.48 | + + +[주] +① 본 품은 강화유리문의 플로어힌지 설치 기준이다. +② 본 품은 플로어힌지 및 로트 설치를 포함한다. +③ 공구손료 및 경장비(용접기, 전동드릴 등)의 기계경비는 인력품의 2%로 계상한다. + +### 10-2-3 도어록 설치('20년 보완) + +(10개소당) + +| 구분 | 단위 | 수량 | | | +|---|---|---|---|---| +| | | 일반도어록 | | 디지털도어록 | +| | | 목재창호 | 강재창호 | 강재창호 | +| 창호공 | 인 | 0.31 | 0.24 | 0.43 | + + +[주] +① 본 품은 목재 및 강재창호의 도어록 기준이다. +② 일반도어록은 레버형, 원형 기준이다. +③ 본 품은 손잡이 및 캐치박스 설치를 포함하며, 목재창호는 구멍뚫기를 포함한다. +④ 공구손료 및 경장비(전동드릴, 절단기 등)의 기계경비는 다음을 적용한다. + +| 구분 | 목재창호 | 강재창호 | +|---|---|---| +| 인력품의 | 4% | 2% | From af8bfa4d7798843e1f8139c32d1d9aeeddc5cf69 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:09 +0900 Subject: [PATCH 11/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B8=B0=EA=B3=84=EC=84=A4=EB=B9=84=201?= =?UTF-8?q?=EC=9E=A5=201-03=5F=EC=8A=A4=ED=85=8C=EC=9D=B8=EB=A6=AC?= =?UTF-8?q?=EC=8A=A4=5F=EA=B0=95=EA=B4=80=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../제01장_배관공사/1-03_스테인리스_강관.md | 185 +++++++++++++++++- 1 file changed, 182 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-03_스테인리스_강관.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-03_스테인리스_강관.md index e1fe9221..cfac73ea 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-03_스테인리스_강관.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-03_스테인리스_강관.md @@ -5,10 +5,189 @@ PDF쪽: 706~709 인쇄쪽: 650~653 시작표지: 1-3 스테인리스 강관 끝표지: 1-4 주철관 -상태: 대기 -작성: +상태: 검증대기 +작성: main_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 1-3 스테인리스 강관 + +### 1-3-1 용접접합('92, '13, '19년 보완) + +(용접개소당) + +| 규격(㎜) | 용접공(인) | 규격(㎜) | 용접공(인) | +|---|---|---|---| +| ø6 | 0.036 | 65 | 0.119 | +| 8 | 0.040 | 80 | 0.135 | +| 10 | 0.045 | 90 | 0.151 | +| 15 | 0.050 | 100 | 0.167 | +| 20 | 0.057 | 125 | 0.199 | +| 25 | 0.066 | 150 | 0.231 | +| 32 | 0.077 | 200 | 0.295 | +| 40 | 0.084 | 250 | 0.359 | +| 50 | 0.099 | 300 | 0.423 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 20%를 감한다. | | | + + +[주] +① 본 품은 TIG용접으로 배관용 스테인리스 강관을 접합하는 기준이다. +② 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 본 품의 4%로 계상하고, 고소작업대(시저형)시공의 경우 13%로 계상한다. +③ 용접접합에 필요한 자재는 별도 계상한다. +④ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. + +[참고자료] +◦ TIG용접 소모재료 + +(용접개소당) + +| 규격(㎜) | 용접봉(㎏) | Argon(ℓ) | +|---|---|---| +| ø15 | 0.007 | 64 | +| 20 | 0.013 | 95 | +| 25 | 0.020 | 129 | +| 40 | 0.040 | 191 | +| 50 | 0.055 | 265 | +| 65 | 0.168 | 343 | +| 80 | 0.213 | 430 | +| 90 | 0.257 | 565 | +| 100 | 0.313 | 699 | +| 125 | 0.443 | 1,098 | +| 150 | 0.601 | 1,285 | +| 200 | 1.007 | 2,170 | +| 250 | 1.455 | 3,060 | +| 300 | 2.070 | 3,945 | + +### 1-3-2 용접배관('92, '13, '19, '25년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(m) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | ø6 | 127 | +| | | | 8 | 123 | +| | | | 10 | 103 | +| | | | 15 | 95 | +| | | | 20 | 82 | +| | | | 25 | 58 | +| | | | 32 | 48 | +| | | | 40 | 45 | +| | | | 50 | 35 | +| | | | 65 | 30 | +| | | | 80 | 25 | +| | | | 90 | 20 | +| | | | 100 | 18 | +| | | | 125 | 14 | +| | | | 150 | 12 | +| 배관공
보통인부 | 인
인 | 4
1 | 200 | 11 | +| | | | 250 | 8 | +| | | | 300 | 6 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다.
- 시공위치에 따라 시공량에 다음 요율을 적용한다. | | | | + + + + +| 시공위치 | 화장실배관 | 기계실배관 | 옥외배관(암거내) | +|---|---|---|---| +| 요율 | - 17% | - 23% | + 11% | +[주] +① 본 품은 배관용 스테인리스 강관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지철물설치, 절단, 배관(가용접), 배관시험을 포함한다. +③ 밸브류 설치품은 ‘[기계설비부문] 5-1-1 일반밸브 및 콕류 설치’를 적용하고, 관이음부속류의 설치품은 본 품에 포함되어 있다. +④ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +⑤ 단열 지지대 및 관 지지대 설치 시에는 별도 계상한다. +⑥ Bending가공이 필요한 경우에는 별도 계상한다. +⑦ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 본 품의 2%로 계상하고, 고소작업대(시저형)시공의 경우 10%로 계상한다. +⑧ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. + +### 1-3-3 그루브조인트식 접합 및 배관('25년 신설) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(m) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | 25 | 57 | +| | | | 32 | 45 | +| | | | 40 | 40 | +| | | | 50 | 30 | +| | | | 65 | 26 | +| | | | 80 | 20 | +| | | | 90 | 18 | +| | | | 100 | 15 | +| | | | 125 | 12 | +| | | | 150 | 10 | +| 배관공
보통인부 | 인
인 | 4
1 | 200 | 9 | +| | | | 250 | 7 | +| | | | 300 | 6 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다.
- 시공위치에 따라 시공량에 다음 요율을 적용한다. | | | | + + + + +| 시공위치 | 화장실배관 | 기계실배관 | 옥외배관(암거내) | +|---|---|---|---| +| 요율 | - 17% | - 23% | + 11% | +[주] +① 본 품은 배관용 스테인리스 강관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지철물설치, 절단, 그루브 홈가공, 배관 및 그루브 접합, 배관시험을 포함한다. +③ 밸브류 설치품은 ‘[기계설비부문] 5-1-1 일반밸브 및 콕류 설치’를 적용하고, 관이음부속류의 설치품은 본 품에 포함되어 있다. +④ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +⑤ 단열 지지대 및 관 지지대 설치 시에는 별도 계상한다. +⑥ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 본 품의 2%로 계상하고, 고소작업대(시저형)시공의 경우 10%로 계상한다. +⑦ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. + +### 1-3-4 프레스식 접합 및 배관('92, '13, '15, '19, '25년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(m) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | 13SU | 80 | +| | | | 20 | 60 | +| | | | 25 | 50 | +| | | | 30 | 40 | +| | | | 40 | 35 | +| | | | 50 | 32 | +| | | | 60 | 25 | +| | | | 75 | 21 | +| | | | 80 | 16 | +| | | | 100 | 14 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다.
- 시공위치에 따라 시공량에 다음 요율을 적용한다. | | | | + + + + +| 시공위치 | 화장실배관 | 기계실배관 | 옥외배관(암거내) | +|---|---|---|---| +| 요율 | - 17% | - 23% | +11% | +[주] +① 본 품은 일반 배관용 스테인리스 강관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지철물설치, 절단, 배관 및 프레스 접합, 배관시험을 포함한다. +③ 밸브류 설치품은 ‘[기계설비부문] 5-1-1 일반밸브 및 콕류 설치’를 적용하고, 관이음부속류의 설치품은 본 품에 포함되어 있다. +④ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +⑤ 단열 지지대 및 관 지지대 설치 시에는 별도 계상한다. +⑥ Bending가공이 필요한 경우에는 별도 계상한다. +⑦ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 인력품의 2%(인력시공), 10%(자체 추진 고소작업대(시저형)시공)로 계상한다. +⑧ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. + +### 1-3-5 주름관 접합 및 배관('92, '13, '19, '25년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 시공량(m) | | +|---|---|---|---|---| +| | | | ø15㎜ | ø20㎜ | +| 배관공
보통인부 | 인
인 | 2
1 | 50 | 45 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다. | | | | + + +[주] +① 본 품은 스테인리스 주름관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지철물설치, 절단, 배관 및 접합, 배관시험을 포함한다. +③ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +④ 단열 지지대 및 관 지지대 설치 시에는 별도 계상한다. +⑤ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 인력품의 2%(인력시공), 10%(자체 추진 고소작업대(시저형)시공)로 계상한다. +⑥ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. From d1e1fd5dc828f826b79f5eb20705ee0ef47ad8fd Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:09 +0900 Subject: [PATCH 12/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B1=B4=EC=B6=95=2010-3=20=EC=9C=A0?= =?UTF-8?q?=EB=A6=AC=20=EC=9E=91=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit - PDF 688~689쪽(인쇄 632~633쪽) · pum_md_tool check 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 Co-Authored-By: Claude Opus 5 (1M context) Claude-Session: https://claude.ai/code/session_016WRFJmmhPi4exAzHgPZHMT --- .../제10장_창호_및_유리공사/10-03_유리.md | 55 ++++++++++++++++++- 1 file changed, 52 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-03_유리.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-03_유리.md index d5bec222..8c238c4d 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-03_유리.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/03_건축부문/제10장_창호_및_유리공사/10-03_유리.md @@ -5,10 +5,59 @@ PDF쪽: 688~689 인쇄쪽: 632~633 시작표지: 10-3 유리 끝표지: 제11장 칠공사 -상태: 대기 -작성: +상태: 검증대기 +작성: sub_laptop_3 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 10-3 유리 + +### 10-3-1 창호유리 설치('14, '20, '26년 보완) + +(㎡당) + +| 구분
(두께) | 판유리 | | 복층유리 | | +|---|---|---|---|---| +| | 유리공(인) | 보통인부(인) | 유리공(인) | 보통인부(인) | +| 3mm이하 | 0.072 | 0.011 | - | - | +| 5mm이하 | 0.083 | 0.013 | - | - | +| 9mm이하 | 0.095 | 0.015 | - | - | +| 12mm이하 | 0.124 | 0.017 | 0.103 | 0.016 | +| 16mm이하 | - | - | 0.113 | 0.017 | +| 18mm이하 | - | - | 0.118 | 0.018 | +| 22mm이하 | - | - | 0.120 | 0.019 | +| 24mm이하 | - | - | 0.124 | 0.020 | +| 28mm이하 | - | - | 0.133 | 0.021 | +| 30mm이하 | - | - | 0.135 | 0.023 | +| 36mm이하 | - | - | 0.141 | 0.024 | +| 40mm이하 | - | - | 0.145 | 0.025 | +| 44mm이하 | - | - | 0.148 | 0.026 | +| 52mm이하 | - | - | 0.154 | 0.026 | + + +[주] +① 본 품은 일반창호를 유리끼우기 실내공사 기준이다. +② 복층유리 두께 28mm초과는 3중유리 기준이다. +③ 본 품은 유리끼우기, 누름대 설치, 실링재 도포, 유리닦기 및 마무리 작업을 포함한다. +④ 특수창호 및 특수유리(접합유리 등)인 경우에는 별도 계상한다. + +### 10-3-2 커튼월유리 설치('14, '20, '26년 보완) + +(㎡당) + +| 구분 | 단위 | 수량 | | | | | | +|---|---|---|---|---|---|---|---| +| | | 12㎜이하 | 16㎜이하 | 18㎜이하 | 22㎜이하 | 24㎜이하 | 28㎜이하 | +| 유리공 | 인 | 0.120 | 0.131 | 0.137 | 0.139 | 0.145 | 0.155 | +| 보통인부 | 인 | 0.020 | 0.021 | 0.022 | 0.023 | 0.024 | 0.025 | + + +[주] +① 본 품은 커튼월 프레임에 구조용실란트를 사용하여 복층유리를 부착하는 기준이다. +② 본 품은 노튼테이프 설치, 유리 붙이기, 구조실란트 및 방수실링재 도포, 유리닦기 및 마무리 작업을 포함한다. +③ 비계매기 또는 고소작업차 비용은 필요시 별도 계상한다. +④ 특수창호 및 특수유리(접합유리, 3중유리 등)인 경우에는 별도 계상한다. +⑤ 외벽의 높이에 따른 할증은 ‘[공통부문] 1-4-5 위험’을 따른다. From 7ff26c564fe72a736530ba0558fb3c533f86da55 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:10 +0900 Subject: [PATCH 13/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B8=B0=EA=B3=84=EC=84=A4=EB=B9=84=201?= =?UTF-8?q?=EC=9E=A5=201-04=5F=EC=A3=BC=EC=B2=A0=EA=B4=80=20=EC=9E=91?= =?UTF-8?q?=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../제01장_배관공사/1-04_주철관.md | 56 ++++++++++++++++++- 1 file changed, 53 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-04_주철관.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-04_주철관.md index dff311c4..bd3e3875 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-04_주철관.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-04_주철관.md @@ -5,10 +5,60 @@ PDF쪽: 710 인쇄쪽: 654 시작표지: 1-4 주철관 끝표지: 1-5 경질관 -상태: 대기 -작성: +상태: 검증대기 +작성: main_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 1-4 주철관 + +### 1-4-1 기계식접합 및 배관('96, '01, '13, '19, '25년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(접합개소) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | ø50 | 18 | +| | | | 65 | 14 | +| | | | 75 | 13 | +| | | | 100 | 10 | +| | | | 125 | 8.5 | +| | | | 150 | 7.5 | +| | | | 200 | 6.0 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다. | | | | + + +[주] +① 본 품은 배수용 주철관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지철물설치, 절단, 배관 및 접합, 배관시험을 포함한다. +③ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +④ 단열 지지대 및 관 지지대 설치시에는 별도 계상한다. +⑤ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 인력품의 2%(인력시공), 10%(자체 추진 고소작업대(시저형)시공)로 계상한다. +⑥ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. + +### 1-4-2 수밀밴드 접합 및 배관('13년 신설, '19, '25년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(접합개소) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | ø50 | 20 | +| | | | 65 | 16 | +| | | | 75 | 14 | +| | | | 100 | 11 | +| | | | 125 | 9.0 | +| | | | 150 | 7.7 | +| | | | 200 | 6.3 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다. | | | | + + +[주] +① 본 품은 배수용 주철관의 노허브(no-hub)관을 접합하는 기준이다. +② 인서트(거푸집용), 지지철물설치, 절단, 배관 및 접합, 배관시험을 포함한다. +③ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +④ 단열 지지대 및 관 지지대 설치시에는 별도 계상한다. +⑤ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 인력품의 2%(인력시공), 10%(자체 추진 고소작업대(시저형)시공)로 계상한다. +⑥ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. From b954582f91e2e6f1b2b15f3d3b141e13b7bbec64 Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:11 +0900 Subject: [PATCH 14/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B8=B0=EA=B3=84=EC=84=A4=EB=B9=84=201?= =?UTF-8?q?=EC=9E=A5=201-05=5F=EA=B2=BD=EC=A7=88=EA=B4=80=20=EC=9E=91?= =?UTF-8?q?=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../제01장_배관공사/1-05_경질관.md | 86 ++++++++++++++++++- 1 file changed, 83 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-05_경질관.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-05_경질관.md index a281887c..8a156258 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-05_경질관.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-05_경질관.md @@ -5,10 +5,90 @@ PDF쪽: 711~712 인쇄쪽: 655~656 시작표지: 1-5 경질관 끝표지: 1-6 연질관 -상태: 대기 -작성: +상태: 검증대기 +작성: main_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 1-5 경질관 + +### 1-5-1 접착제 접합 및 배관('13, '19, '25년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(m) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | ø30 | 45 | +| | | | 35 | 40 | +| | | | 40 | 37 | +| | | | 50 | 31 | +| | | | 65 | 25 | +| | | | 75 | 23 | +| | | | 100 | 18 | +| | | | 125 | 15 | +| | | | 150 | 13 | +| | | | 200 | 11 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다. | | | | + + +[주] +① 본 품은 일반용 경질 폴리염화 비닐관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지물 설치, 절단, 배관 및 접합, 배관시험을 포함한다. +③ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +④ 단열 지지대 및 관 지지대 설치시에는 별도 계상한다. +⑤ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 인력품의 2%(인력시공), 10%(자체 추진 고소작업대(시저형)시공)로 계상한다. +⑥ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. + +### 1-5-2 고무링 캡조임 접합 및 배관(일반 PVC)('13년 신설, '19, '25년 보완) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(m) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | ø30 | 105 | +| | | | 35 | 98 | +| | | | 40 | 90 | +| | | | 50 | 80 | +| | | | 65 | 70 | +| | | | 75 | 55 | +| | | | 100 | 42 | +| | | | 125 | 35 | +| | | | 150 | 28 | +| | | | 200 | 23 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다. | | | | + + +[주] +① 본 품은 일반용 경질 폴리염화 비닐관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지물 설치, 절단, 배관 및 접합, 배관시험을 포함한다. +③ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +④ 단열 지지대 및 관 지지대 설치시에는 별도 계상한다. +⑤ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 인력품의 2%(인력시공), 10%(자체 추진 고소작업대(시저형)시공)로 계상한다. +⑥ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. + +### 1-5-3 고무링 캡조임 접합 및 배관(고강도PVC)('25년 신설) + +(일당) + +| 구분 | 단위 | 수량 | 관규격(㎜) | 시공량(m) | +|---|---|---|---|---| +| 배관공
보통인부 | 인
인 | 3
1 | 50 | 75 | +| | | | 65 | 65 | +| | | | 75 | 50 | +| | | | 100 | 38 | +| | | | 125 | 32 | +| | | | 150 | 25 | +| | | | 200 | 20 | +| 비고 | - 자체 추진 고소작업대(시저형)시공의 경우 시공량의 26%를 가산한다. | | | | + + +[주] +① 본 품은 고강도 경질 폴리염화비닐관의 옥내일반배관 기준이다. +② 인서트(거푸집용), 지지물 설치, 절단, 배관 및 접합, 이탈방지장치(클램프 등) 설치, 배관시험을 포함한다. +③ 현장여건에 따라 콘크리트용 인서트를 사용할 경우 ‘[건축부문] 8-1-4 인서트(Insert) 설치’를 따른다. +④ 단열 지지대 및 관 지지대 설치시에는 별도 계상한다. +⑤ 공구손료 및 경장비(절단기, 자체 추진 고소작업대(시저형) 등)의 기계경비는 인력품의 2%(인력시공), 10%(자체 추진 고소작업대(시저형)시공)로 계상한다. +⑥ 자체 추진 고소작업대(시저형)의 이동을 위한 크레인, 지게차 등의 비용은 별도 계상한다. From f2ce2ab732f1099da2a1b5a77b9d6c42ce711f2e Mon Sep 17 00:00:00 2001 From: umsangdon Date: Sat, 19 Sep 2026 03:30:12 +0900 Subject: [PATCH 15/15] =?UTF-8?q?knowledge(=ED=92=88=EC=85=88md):=20?= =?UTF-8?q?=EA=B1=B4=EC=84=A4=20=EA=B8=B0=EA=B3=84=EC=84=A4=EB=B9=84=201?= =?UTF-8?q?=EC=9E=A5=201-06=5F=EC=97=B0=EC=A7=88=EA=B4=80=20=EC=9E=91?= =?UTF-8?q?=EC=84=B1?= MIME-Version: 1.0 Content-Type: text/plain; charset=UTF-8 Content-Transfer-Encoding: 8bit --- .../제01장_배관공사/1-06_연질관.md | 56 ++++++++++++++++++- 1 file changed, 53 insertions(+), 3 deletions(-) diff --git a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-06_연질관.md b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-06_연질관.md index 93909482..0443f47b 100644 --- a/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-06_연질관.md +++ b/resources/knowledge/original/원가계산/건설공사_표준품셈/본문/04_기계설비부문/제01장_배관공사/1-06_연질관.md @@ -5,10 +5,60 @@ PDF쪽: 712~713 인쇄쪽: 656~657 시작표지: 1-6 연질관 끝표지: 제2장 덕트공사 -상태: 대기 -작성: +상태: 검증대기 +작성: main_desktop_1 검증: 원천: 글자층 -기계검사: +기계검사: 통과 · ①수 결손 0 허구 0 · ②글자 빠짐 0 더함 0 확정지문: --- + +## 1-6 연질관 + +### 1-6-1 폴리부틸렌(PB) 일반접합 및 배관('96년 신설, '13, '19년 보완) + +(m당) + +| 구분 | 단위 | 수량 (규격) | | +|---|---|---|---| +| | | ø16mm | ø20mm | +| 배관공 | 인 | 0.038 | 0.042 | +| 보통인부 | 인 | 0.015 | 0.017 | + + +[주] +① 본 품은 폴리부틸렌(PB)관의 급수, 급탕용 배관 기준이다. +② 절단, 배관 및 고정철물 설치, 접합, 배관시험을 포함한다. +③ 공구손료 및 경장비의 기계경비는 인력품의 1%로 계상한다. + +### 1-6-2 폴리부틸렌(PB) 이중관 접합 및 배관('13, '19년 보완) + +(m당) + +| 구분 | 단위 | 수량 (규격) | | +|---|---|---|---| +| | | ø16mm | ø20mm | +| 배관공 | 인 | 0.048 | 0.053 | +| 보통인부 | 인 | 0.021 | 0.023 | + + +[주] +① 본 품은 합성수지제 휨(가요) 전선관 중 CD(Combine Duct)관 내에 폴리부틸렌(PB)관이 삽입된 이중관의 옥내바닥배관 기준이다. +② 절단, 배관 및 고정철물 설치, 접합, 배관시험을 포함한다. +③ 공구손료 및 경장비의 기계경비는 인력품의 1%로 계상한다. + +### 1-6-3 가교화 폴리에틸렌관 접합 및 배관('13, '19년 보완) + +(m당) + +| 구분 | 단위 | 수량 (규격) | | +|---|---|---|---| +| | | ø16mm | ø20mm | +| 배관공 | 인 | 0.029 | 0.036 | +| 보통인부 | 인 | 0.014 | 0.018 | + + +[주] +① 본 품은 가교화 폴리에틸렌(PE-X)관의 옥내난방배관 기준이다. +② 절단, 배관 및 고정철물 설치, 접합, 배관시험을 포함한다. +③ 공구손료 및 경장비의 기계경비는 인력품의 1%로 계상한다.